|
Following is the revised Section
1701, Special Inspections, as it appears in the 1997 Edition
of the Uniform Building Code:
SECTION 1701 SPECIAL
INSPECTIONS
1701.1 General. In addition to the inspections required
by Section 108, the owner or the engineer or architect of record
acting as the owners agent shall employ one or more special
inspectors who shall provide inspections during construction
on the types of work listed under Section 1701.5.
EXCEPTION: The building official may waive the requirement
for the employment of a special inspector if the construction
is of a minor nature.
-
- 1701.2 Special
Inspector. The special
inspector shall be a qualified person who shall demonstrate competence,
to the satisfaction of the building official, for inspection
of the particular type of construction or operation requiring
special inspection.
-
- 1701.3 Duties and Responsibilities
of the Special Inspector.
The special inspector shall observe the work assigned for conformance
with the approved design drawings and specifications. The special
inspector shall furnish inspection reports to the building official,
the engineer or architect of record, and other designated persons.
All discrepancies shall be brought to the immediate attention
of the contractor for correction, then, if uncorrected, to the
proper design authority and to the building official. The special
inspector shall submit a final signed report stating whether
the work requiring special inspections was, to the best of the
inspectors knowledge, in conformance with the approved
plans and specifications and the applicable workmanship provisions
of this code.
-
- 1701.4 Standards of Quality. The standards listed below labeled a
"U.B.C. standard" are also listed in Chapter 35, Part
II, and are part of this code. The other standards listed below
are recognized standards. (See Sections 3505 and 3504)
- 1. Concrete
- ASTM C 94, Ready-mixed Concrete
- 2. Connections
- Specifications for Structural
Joints using ASTM A 325 or A 490 Bolts-Load and Resistance Factor
Design, Research Council of Structural Connections, Section 1071.5,
Item 6.Specification for Structural Joints using ASTM A 325 or
A 490 Bolts-Allowable Stress Design, Research Council of Structural
Connections, Section 1701.5, Item 6.
- 3. Spray-applied Fire-resistive
Materials.
- U.B.C. Standard 7-6, Thickness
and Density Determination for Spray-applied Materials.
-
- 1701.5 Types of
Work. Except as provided
in Section 1701.1, the types of work listed below shall be inspected
by a special inspector.
- 1. Concrete. During the taking of test specimens and
placing of reinforced concrete. See Item 12 for shotcrete.
- EXCEPTIONS:
- Concrete for foundations conforming
to minimum requirements of Table 18-I-D or for Group R, Division
3 or Group U, Division 1 Occupancies, provided the building official
finds that a special hazard does not exist.
- For foundation concrete, other
than cast-in-place drilled piles or caissons, where the structural
design is based on an fc no greater than 2,500 pounds per
square inch (psi) (17.2 MPa).
- Nonstructural slabs on grade,
including prestressed slabs on grade when effective prestress
in concrete is less than 150 psi. (1.03 MPa).
- Site work concrete fully supported
on earth and concrete where no special hazard exists.
- 2. Bolts installed in concrete. Prior to and during the placement of
concrete around bolts when stress increases permitted by Footnote
5 of Table 19-D or Section 1923 are utilized.
- 3. Special moment-resisting
concrete frame. For moment
resisting frames resisting design seismic load in structures
within seismic Zones 3 and 4, the special inspector shall provide
reports to the person responsible for the structural design and
shall provide continuous inspection of the placement of the reinforcing
and concrete.
- 4. Reinforcing steel and
prestressing steel tendons.
- 4.1 During all stressing and
grouting of tendons in prestressed concrete.
-
- 4.2 During placing of reinforcing
steel and prestressing tendons for all concrete required to have
special inspection by Item 1.
-
- EXCEPTION: The special inspector need not be present
continuously during placing of reinforcing steel and prestressing
tendons, provided the special inspector has inspected for conformance
with the approved plans prior to the closing of forms or the
delivery of concrete to the job site.
-
- 5. Structural welding.
- 5.1 General. During the welding of any member or connection
which is designed to resist loads and forces required by this
code.
- EXCEPTIONS:
- 1. Welding done in an approved
fabricators shop in accordance with Section 1701.7.
-
- 2. The special inspector need
not be continuously present during welding of the following items,
provided the materials, qualifications of welding procedures
and welders are verified prior to the start of work; periodic
inspections are made of work in progress; and a visual inspection
of all welds is made prior to completion or prior to shipment
of shop welding:
- 2.1 Single-pass fillet welds
not exceeding 5/16 inch (7.9 mm) in size.
- 2.2 Floor and roof deck welding
- 2.3 Welded studs when used for
structural diaphragm or composite systems.
- 2.4 Welded sheet steel for cold-formed
steel framing members such as studs and joists.
- 2.5 Welding of stairs and railing
systems.
-
- 5.2 Special moment-resisting
steel frames. During
the welding of special moment-resisting steel frames. In addition
to Item 5.1 requirements above, nondestructive testing as required
by Section 1703 of this code.
- 5.3 Welding of reinforcing
steel. During the welding
of reinforcing steel.
-
- EXCEPTION: The special inspector need not be continuously
present during the welding of ASTM A706 reinforcing steel not
larger than No. 5 bars used for embedments, provided the materials,
qualifications of welding procedures and welders are verified
prior to the start of work; periodic inspections are made of
work in progress; and a visual inspection of all welds is made
prior to completion or prior to shipment of shop welding.
-
- 6. High-strength bolting.
The inspection of high-strength
A 325 and A 490 bolts shall be in accordance with approved nationally
recognized standards and the requirements of this section. While
the work is in progress, the special inspector shall determine
that the requirements for bolt, nuts, washers and paint; bolted
parts, and installation and tightening in such standards are
met. Such inspections shall be performed on a periodic basis
in accordance with the requirements of Section 1701.6. The special
inspector shall observe the calibration procedures when such
procedures are required by the plans or specifications and shall
monitor the installation of bolts to determine that all plies
of connected materials have been drawn together and that the
selected procedure is properly used to tighten all bolts.
-
- 7. Structural masonry.
- 7.1 For masonry, other than
fully grouted open-end hollow-unit masonry, during preparation
and taking of any required prisms or test specimens, placing
of all masonry units, placement of reinforcement, inspection
of grout space, immediately prior to closing of cleanouts, and
during all grouting operations.
- EXCEPTION: For hollow-unit masonry where the fm
is no more than 1,500 psi (10.34 MPa) for concrete units or 2,600
psi (17.93 MPa) for clay units, special inspection may be performed
as required for fully grouted open-end hollow-unit masonry specified
in Item 7.2 below.
-
- 7.2 For fully grouted open-end
hollow-unit masonry during preparation and taking of any required
prisms or test specimens, at the start of laying units, after
the placement of reinforcing steel, grout space prior to each
grouting operation, and during all grouting operations.
- EXCEPTION: Special inspection as required in Items
7.1 and 7.2 above need not be provided when design stresses have
been adjusted as specified in Chapter 21 to permit noncontinuous
inspection.
-
- 8. Reinforced gypsum concrete.
When cast-in-place Class
B gypsum concrete is being mixed and placed.
-
- 9. Insulating concrete fill. During the application of insulating
concrete fill when used as part of a structural system.
- EXCEPTION: The special inspections may be limited
to an initial inspection to check the deck surface and placement
of reinforcing. The special inspector shall supervise the preparation
of compression test specimens during this initial inspection.
-
- 10. Spray-applied fire-resistive
materials. As required
by U.B.C. Standard 7-6.
-
- 11. Piling, drilled piers
and caissons. During
driving and testing of piles and construction of cast-in-place
drilled piles or caissons. See Items 1 and 4 for concrete and
reinforcing steel inspection.
-
- 12. Shotcrete. During the taking of test specimens
and placing of all shotcrete and as required by Sections 1924.10 and 1924.11.
- EXCEPTION: Shotcrete work fully supported on earth,
minor repairs and when, in the opinion of the building official,
no special hazard exists.
-
- 13. Special grading, excavation
and filling. During earth-work
excavations, grading and filling operations inspection to satisfy
requirements of Chapter 18 and Appendix Chapter 33 of this code.
-
- 14. Smoke-control system.
- 14.1 During erection of ductwork
and prior to concealment for the purposes of leakage testing
and recording of device location.
-
- 14.2 Prior to occupancy and
after sufficient completion for the purposes of pressure difference
testing, flow measurements, and detection and control verification.
-
- 15. Special cases. Work which, in the opinion of the building
official, involves unusual hazards or conditions.
-
- 1701.6 Continuous
and Periodic Special Inspection
-
- 1701.6.1 Continuous special
inspection. Continuous
special inspection means that the special inspector is on the
site at all times observing the work requiring special inspection.
-
- 1701.6.2 Periodic special
inspection. Some inspections
may be made on a periodic basis and satisfy the requirements
of continuous inspection, provided this periodic scheduled inspection
is performed as outlined in the project plans and specifications
and approved by the building official.
-
- 1701.7 Approved Fabricators Special inspections required by this
section and elsewherein this code are not required where the
work is done on the premises of a fabricator registered and approved
by the building official to perform such work without special
inspection. The certificate of registration shall be subject
to revocation by the building official if it is found that any
work done pursuant to the approval is in violation of this code.
The approved fabricator shall submit a certificate of compliance
that the work was performed in accordance with the approved plans
and specifications to the building official and the engineer
or architect of record. The approved fabricators qualifications
shall be contingent on compliance with the following:
- The fabricator has developed
and submitted a detailed fabrication procedure manual reflecting
key quality control procedures that will provide a basis for
inspection control of workmanship and fabricator plant.
- Verification of the fabricators
quality control capabilities, plant and personnel as outlined
in the fabrication procedural manual shall be by an approved
inspection or quality control agency.
- Periodic plant inspections shall
be conducted by an approved inspection or quality control agency
to monitor the effectiveness of the quality control program.
- It shall be the responsibility
of the inspection or quality control agency to notify the approving
authority in writing of any change to the procedural manual.
Any fabricator approval may be revoked for just cause. Re-approval
of the fabricator shall be contingent on compliance with quality
control procedures during the past year.
Reproduced from the
1997 Edition of the Uniform Building Code, Copyright 1997, with
permission of the publisher, the Intentional Conference of Building
Officials. |